Parameter List

Sources: 05.ES610_参数列表.html (the “Appendix D Parameter List” of the ES610 comprehensive manual) and 610调试参数-华美达.html

Usage notes

When FP-00 is set to a nonzero value, a user password is enabled. In function-parameter mode and user-changed-parameter mode, the parameter menu is accessible only after the correct password is entered. To remove the password, set FP-00 to 0.

The user password only locks panel operation. After entering the correct password, the valid session for reading/writing via the keypad lasts one hour; after that, the password must be re-entered. Communication operations can read and write parameters without a password (except for the FP group).

The “Change” column uses the following symbols:

SymbolMeaning
Real-timeChangeable in both stop and run states.
Stop-onlyCannot be changed while running.
Read-onlyRead-only detected value.
⚠️

The parameter tables were extracted from PDF-to-HTML conversion. Long tables that cross pages may have misaligned cells. Before batch-writing parameters in the field, verify against the original manufacturer PDF or the drive’s actual display.

Parameter table fields

FieldDescription
ParameterDrive parameter number, e.g. F0-00, F1-02, A3-01.
Communication addressParameter’s communication address.
NameParameter name.
Setting valueSettable values, enumerations, or read-only range.
DefaultFactory default.
UnitParameter unit.
ChangeWhether the value can be changed while running, or whether it is read-only / factory.

F0 group: basic operation parameters

ParameterNameSetting valueDefaultUnitChange
F0-00Model selection1: G-type; 2: P-type1-Read-only
F0-01Control mode1: closed-loop vector (FVC)1-Stop-only
F0-02Command source0: operator panel; 1: terminal; 2: communication0-Real-time
F0-03Main frequency source0: digital UP/DOWN (not stored); 1: digital UP/DOWN (stored); 2: AI1; 3: AI2; 4: AI3; 6: multi-speed; 9: communication0-Stop-only
F0-04Auxiliary frequency source Y0–9 (same as F0-03)0-Stop-only
F0-05Auxiliary frequency Y range reference0: relative to max frequency; 1: relative to main source X0-Real-time
F0-06Auxiliary frequency Y range0%–100%100%Real-time
F0-07Frequency source selection0–30-Real-time
F0-08Preset frequency0.00Hz–300.00Hz100.00HzReal-time
F0-09Rotation direction0: same; 1: reversed0-Stop-only
F0-10Max frequency50.00Hz–300.00Hz200.00HzStop-only
F0-11Upper-frequency source0: F0-12; 1–5: AI/communication0-Stop-only
F0-12Upper frequencyF0-14Hz–F0-10Hz200.00HzReal-time
F0-13Upper-frequency bias0.00Hz–F0-10Hz0.00HzReal-time
F0-14Lower frequency0.00Hz–F0-12Hz0.00HzReal-time
F0-15Carrier frequency2.0kHz–8.0kHz5.0kHzStop-only
F0-17Acceleration time0ms–65000ms20000msReal-time
F0-18Deceleration time0ms–65000ms20000msReal-time

F1 group: motor parameters

ParameterNameSetting valueDefaultUnitChange
F1-00Motor type0–6553514101-Stop-only
F1-01Motor rated power0.00kW–650.00kW0.75kWStop-only
F1-02Motor rated voltage0V–800V380VStop-only
F1-03Motor rated current0.00A–650.00A4.70AStop-only
F1-04Motor rated frequency0.00Hz–300.00Hz133.00HzRead-only
F1-05Motor rated speed0–3000 rpm1500rpmStop-only
F1-06Motor rated torque0.00Nm–650.00Nm2.39NmStop-only
F1-07Motor max torque0.00Nm–650.00Nm7.16NmStop-only
F1-08Motor inertia0.00–650.001.30-Stop-only
F1-09Motor pole pairs0–104-Stop-only
F1-10Torque constant Kt0.00–650.000.51-Real-time
F1-11Synchronous D-axis inductance0.00–655.353.87-Stop-only
F1-12Synchronous Q-axis inductance0.00–655.353.27-Stop-only
F1-13Synchronous stator resistance0.000Ω–65.535Ω0.500ΩStop-only
F1-14Electrical constant Te0.00–655.356.54-Stop-only
F1-15Synchronous back-EMF0V–65535V300VRead-only
F1-16Tuning selection0: none; 1: no-load static identification; 2: no-load dynamic identification; 3: no-load initial-angle identification; 4: no-load R/L identification; 5: no-load back-EMF identification0-Stop-only
F1-17Max speed0–65535 rpm6000rpmStop-only
F1-18Back-EMF coefficient0.00–655.3533.30-Stop-only
F1-19Absolute encoder offset L0–655358192-Stop-only
F1-20Absolute encoder offset H0–655350-Stop-only
F1-21D-axis back-EMF compensation0.0–6553.560.0-Real-time
F1-22Q-axis back-EMF compensation0.0–6553.5100.0-Real-time
F1-23D-axis current-loop P gain0–655351000-Real-time
F1-24D-axis current-loop I compensation0.00–655.352.00-Real-time
F1-25Q-axis current-loop P gain0–655351000-Real-time
F1-26Q-axis current-loop I compensation0.00–655.351.00-Real-time
F1-33Mechanical time constant Tm0.00–655.350.24-Stop-only
F1-34Bus motor model0–655350-Stop-only
F1-35Absolute-encoder function bits0–655350-Stop-only
F1-36Motor max current0.00A–655.35A16.95AStop-only
F1-39Encoder software version0.0–6553.50.0-Read-only
F1-40Absolute-encoder type0–655350-Stop-only

F2 group: speed-loop and servo control

ParameterNameSetting valueDefaultUnitChange
F2-00Speed-loop P gain 10.1–2000.025.0-Real-time
F2-01Speed-loop I time 10.15–512.0031.83-Real-time
F2-02Speed-loop switch speed 10 rpm – F2-05 rpm75rpmReal-time
F2-03Speed-loop P gain 20.1–2000.014.0-Real-time
F2-04Speed-loop I time 20.15–512.0026.53-Real-time
F2-05Speed-loop switch speed 2F2-02 rpm – 20000 rpm150rpmReal-time
F2-06Real-time inertia ratio0.00–120.002.00-Read-only
F2-07Speed-feedback filter time0.1ms–100.0ms2.0msReal-time
F2-08Servo performance mode0: normal; 1: enhanced; 2: high-performance0-Real-time
F2-09Torque upper-limit source (speed mode)0: F2-10; 1–3: AI; 5: communication0-Real-time
F2-10Torque upper limit0.0–250.0200.0-Real-time
F2-11Auto-tune mode0–11-Real-time
F2-12Stiffness level 10–3112-Real-time
F2-13Load inertia-ratio setting0.00–120.001.00-Stop-only
F2-14Stiffness level 2 Kp0–3110-Real-time
F2-15Stiffness level 2 Ki0–3113-Real-time
F2-16Speed-feedforward filter time0.00–64.000.50-Real-time
F2-17Speed feedforward gain0.0–100.00.0-Real-time
F2-19Speed-feedback low-pass cutoff100–40004000-Real-time
F2-20Torque feedforward selection0–11-Real-time
F2-25Torque-feedforward filter time0.00–64.000.50-Real-time
F2-26Torque feedforward gain0.0–200.00.0-Real-time
F2-27PDFF coefficient0.0–1000.0100.0-Real-time
F2-28Speed-feedback selection0–10-Real-time
F2-29Speed-observer coefficient0.0–100.00.0-Real-time
F2-30Speed-observer cutoff10Hz–2000Hz170HzReal-time

A3 group: pressure-control parameters

A3 is the function group specific to the ES610 hydraulic servo system. It covers pressure-mode selection, max speed, system pressure, PID response, pressure release, base flow/pressure, filter times, and other key parameters.

⚠️

Only parameters explicitly referenced in the quick-tuning guide and HMD site parameters are listed. For the full A3 group, refer to the original manufacturer manual.

ParameterNameRangeDefaultUnitChange
A3-00Pressure-mode selection0: speed; 2: analog; 4: pressure PN; 6: CANopen0-Stop-only
A3-01Max speed0–65535-rpmReal-time
A3-02System pressure0 to max pressure (A3-03)-kg/cm²Real-time
A3-03Max pressure0 to sensor range-kg/cm²Real-time
A3-04Group-1 pressure-command rise time0.000s–2.000s-sReal-time
A3-05Group-1 PID P gain Kp0.0–800.0--Real-time
A3-06Group-1 PID I time Ki0.001–10.000--Real-time
A3-07Group-1 PID D time Kd---Real-time
A3-08Max reverse speed (release)0%–100%-%Real-time
A3-09Base flow0.0%–50.0%-%Real-time
A3-10Base pressure0.0–50.0-kg/cm²Real-time
A3-20AI zero-drift auto-correction0–10-Real-time
A3-25Group-1 pressure-rise S-filter0.000s–1.000s-sReal-time
A3-26Group-1 pressure-fall S-filter0.000s–1.000s-sReal-time
A3-29Pressure-loop gain coefficient0.2%–5.00%1.00%Real-time
A3-63High/low-pressure PI switch enable0–10-Real-time
A3-64Group-1 low-pressure control Kp0.0–800.0210-Real-time
A3-65Group-1 low-pressure control Ti0.001–10.0000.5-Real-time
A3-66Group-1 high-pressure control Kp0.0–800.0260-Real-time
A3-67Group-1 high-pressure control Ti0.001–10.0000.02-Real-time
A3-68Low-pressure threshold0.0 to A3-6950-Real-time
A3-69High-pressure thresholdA3-68 to A3-02100-Real-time

A4 group: advanced pressure-control parameters

ParameterNameRangeDefaultUnitChange
A4-02Group-1 pressure-command fall time0.000s–2.000s-sReal-time
A4-03Group-1 flow-command rise time0–5.000s-sReal-time
A4-04Group-1 flow-command fall time0–5.000s-sReal-time
A4-44Pressurize-to-hold PID switch0–70-Real-time
A4-45Feedback-pressure filter for switching into hold0.000s–5.000s0.005sReal-time
A4-46Pressure deviation for switching into hold0.0–10.01kg/cm²Real-time
A4-47Speed ceiling for switching into hold0–1000200rpmReal-time
A4-79Hold detection follows setpoint change0–11-Real-time
A4-80Inertia auto-adjust low-pressure threshold0.0 to A4-8110kg/cm²Real-time
A4-81Inertia auto-adjust high-pressure thresholdA4-80 to A3-0220kg/cm²Real-time
A4-82Inertia ratio at low-pressure threshold0.2 to F2-130.5-Real-time

F4 group: analog I/O parameters

F4 parameters configure ranges, filters, and mappings for AI1–AI4 and AO1–AO2. In pressure mode, F4 works together with A3 to calibrate pressure command, flow command, and pressure feedback.

⚠️

Only F4 parameters explicitly referenced in the quick-tuning guide are listed. For the full F4 group, refer to the original manufacturer manual.

ParameterNameRangeDescription
F4-18AI1 minimum input-Minimum voltage for pressure command, corresponding to AI1 zero drift
F4-19AI1 minimum-input setting0.0%–100.0%Minimum pressure command; default 0.0%
F4-20AI1 maximum input-Maximum voltage for pressure command; typically 10 V
F4-21AI1 maximum-input setting0.0%–100.0%Maximum pressure command; default 100.0%
F4-22AI1 filter time0.000s–10.000sAI1 filter time
F4-23AI2 minimum input-Minimum voltage for flow command, corresponding to AI2 zero drift
F4-24AI2 minimum-input setting0.0%–100.0%Minimum flow command; default 0.0%
F4-25AI2 maximum input-Maximum voltage for flow command; typically 10 V
F4-26AI2 maximum-input setting0.0%–100.0%Maximum flow command; default 100.0%
F4-27AI2 filter time0.000s–10.000sAI2 filter time
F4-28AI3 minimum input-Minimum voltage for pressure feedback, corresponding to AI3 zero drift
F4-29AI3 minimum-input setting0.0%–100.0%Minimum pressure feedback; default 0.0%
F4-30AI3 maximum input-Maximum voltage for pressure feedback; typically 10 V
F4-31AI3 maximum-input setting0.0%–100.0%Maximum pressure feedback; default 100.0%
F4-33AI4 zero-drift correction-AI4 zero-drift correction

HMD quick-tuning parameters

The following are common commissioning parameters for the ES610 drive on HMD injection-molding machines:

ParameterValueDescription
FP-011Parameter reset
A3-201AI zero-drift auto-correction
A3-005CAN5 mode
A3-012500Max speed
A3-0820Reverse speed
A3-090Base flow (check base flow/pressure)
A3-100Base pressure (check base flow/pressure)
A3-040.05Group-1 pressure-command rise time
A4-030.05Group-1 flow-command rise time
A4-100.001Group-2 pressure-command rise S-filter
A4-110.001Group-2 pressure-command fall S-filter
A4-120.001Group-2 flow-command rise time
A4-130.05Group-2 flow-command fall time
A4-140.001Group-2 pressure-command rise time
A4-150.05Group-2 pressure-command fall time
F0-1750 msAcceleration time
F0-1880–150 msDeceleration time (adjustable)
F2-0010.0Speed-loop parameter
F2-10180Torque upper limit
⚠️

These HMD tuning parameters are for a specific site configuration. Other machine types and operating conditions may need adjustment. Refer to the original manufacturer manual and site requirements.

Recommendations for completing the parameter table

This page already covers the deterministic F0, F1, F2 groups and commonly used A3, A4, and F4 parameters. Because the original PDF tables span pages and the HTML uses absolute positioning, achieving an “item-by-item complete parameter table” is best done later using Excel/Word source tables or manually verified CSV; otherwise setting range, min unit, and factory values may be misaligned across columns.