Troubleshooting

Source: 04.ES750N_故障处理.html (the “Troubleshooting” chapter of the ES750N series servo-drive manual)

Restart after a fault

StageActionNotes
When the fault occursView the last three fault timestamps, types, and the frequency/current/bus/DI/DO state at the time of fault on the operator panelUse F9-18F9-44
Before resetIdentify and clear the cause from the fault code on the panel, then resetRefer to the fault-code list for handling

Fault reset

  1. DI reset: set a DI to function 9 (F4-00F4-04=9, fault reset) and drive it active.
  2. Panel reset: confirm F7-02=2 (factory default); the red stop/reset key on the panel resets faults in any operating mode.
  3. Power-cycle reset: disconnect main power, wait until the panel display disappears, then reapply power for automatic reset.
  4. Communication reset: from the host, write “7” (fault reset) to address 2000H to reset after the fault is cleared.
⚠️

Some faults require the cause to be cleared by a setting change before reset, but a successful reset does not mean the change is in effect. Changes that require a power-cycle must be followed by a power-cycle.

Common symptoms and remedies

No.SymptomPossible causeRemedy
1No display on power-upGrid voltage missing or too lowCheck input power
Drive-board switch-mode supply faultyCheck bus voltage
Control-board, drive-board, or keypad cable brokenReseat the 64-pin cable
Buffer resistor damaged / control board or keypad faultyConsult a technician
Rectifier damaged / poor contact between drive and control boardsReseat the 64-pin cable
2Display continuously shows “HC” on power-upComponents on the control board damaged / motor or motor cable grounded / Hall faultConsult a technician
3Shows “HC” and stops immediately after runningFan damaged or stalledReplace fan
External control terminal wiring shortedClear the external short
Motor wiring abnormalRe-verify the drive-to-motor wiring
4Motor does not rotate after the drive runsDrive parameter error (motor params)Restore factory settings and reconfigure; verify F0-01 (control mode) and F0-02 (run mode)
Poor contact between drive and control boardsReseat the connection
Drive-board faultConsult a technician
5DI terminal not effectiveParameter errorRecheck F4-group parameters
Wrong external signalRewire the external signal
Wrong S5 DIP settingConfirm S5 matches actual wiring
Control-board faultConsult a technician
6In closed-loop vector, motor speed cannot increaseEncoder fault / wrong or loose encoder wiring / PG-card faultReplace the encoder and re-verify wiring; replace the PG card; consult a technician
7Drive frequently reports overcurrent and overvoltageMotor parameters incorrectReconfigure motor parameters or run motor identification
Acceleration/deceleration time inappropriateSet appropriate acceleration/deceleration times
Load fluctuationConsult a technician
8Motor coasts during deceleration or cannot brakeEncoder open or overvoltage-stall protection triggeredCheck encoder wiring; if a braking resistor is installed, set F3-23=0 to disable overvoltage stall
9Burnt buffer resistorBraking-resistor lead shorted to chassis / braking transistor blown / bus capacitor blown/shorted / negative bus to groundAdd insulation / replace braking transistor / replace bus capacitor / clear the short

Fault-code list

E002.0: hardware overcurrent

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismAxis 1: instantaneous output current exceeds 2.5 × 1.414 × rated current. Axis 2: exceeds 2 × 1.414 × rated.
CauseVerificationRemedy
Drive-board abnormalCheck for proper grounding and lack of interference; check encoder speed feedbackReplace components causing grounding issues; try replacing the encoder and cable

E002.2: software overcurrent

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismInstantaneous output current exceeds the software overcurrent point
CauseVerificationRemedy
Drive output ground or short circuitCheck for motor or contactor shortReplace components causing grounding issues
Encoder interference or disconnection, or encoder loose/reversed/poor-concentricity causing oscillation overcurrentCheck encoderTune F8-43 encoder interference threshold; try replacing encoder and cable
FVC/SVC without parameter identificationSet motor parameters from nameplate and identifyRun motor-parameter identification
Acceleration time too shortCheck F0-17Increase acceleration time (F0-17)
Overcurrent stall-suppression settings inappropriateCheck F3-19 enable, F3-18 action current, F3-20 gainConfirm enable; recommend F3-18 120%–160%; recommend F3-20 20–40

E005.0: overvoltage

ItemNotes
Default fault level0: coast to stop
ResettableYes
Mechanism1. Motor generating, regenerative energy raises the bus voltage. 2. Input voltage abnormal.
CauseVerificationRemedy
Input grid voltage highMeasure with a multimeterAdjust voltage to normal
Ground shortCheck ground impedanceClear the ground short
Encoder open or poor concentricity causing oscillation overvoltageCheck encoderReplace encoder and cable
Coasting from overspeed on a PMSM causes high back-EMFCheck feedback speed via host softwareLimit max speed or add safety measures
Weak speed loop (acceleration too fast) causes overshoot overvoltageCheck for speed overshootIncrease F0-17; enable torque feedforward and RFG arc
External force driving the motor during accelerationCheck for external forceRemove the external force
No braking unit or resistor installedCheck for braking unit and resistorInstall

E008.0: buffer-resistor fault

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismCounter detects 5 abnormal bus-voltage fluctuations within a set period
CauseVerificationRemedy
Contactor abnormal or frequent rapid power cyclesConfirm input is 342 V AC–418 V AC; confirm no repeated power cyclesContact technical support

E009.1: undervoltage

ItemNotes
Default fault level0: coast to stop
ResettableYes
Mechanism1. Contactor not engaged. 2. Input voltage abnormal, bus voltage below the undervoltage point.
CauseVerificationRemedy
Momentary power lossConfirm input is 342 V AC–418 V ACEnable the “ride-through” function (F9-59)
Drive input voltage out of rangeMeasure input voltageAdjust voltage to normal
Input phase lossMeasure input grid voltage; check rectifier diodesClear phase loss
Bus voltage abnormalUse host software to capture bus voltageContact technical support
Rectifier or inverter drive board abnormalConfirm DC bus voltage with a multimeterContact technical support

E009.3: pre-drive timeout

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismIn an undervoltage state, the bus-voltage ramp-up after motor start did not complete within 5 s
CauseVerificationRemedy
Pre-charge abnormal; start in undervoltageConfirm bus voltage is normal (≈1.414 × input RMS)Wait for the bus to stabilize; check the main contactor/grid

E010.0: drive overload

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismJudged by the drive overload curve
CauseVerificationRemedy
Load too large or motor stalledCheck output current and for motor stallReduce load and check the mechanics
Drive undersizedConfirm drive power is less than motor powerUse a higher-power drive
FVC/SVC without parameter identificationCheck identificationSet nameplate parameters and run identification
Encoder abnormalCheck encoderTry replacing encoder and cable
Synchronous motor demagnetizedMeasure back-EMFReplace the motor
Input voltage low causing high output currentConfirm input is 342 V AC–418 V ACRaise input voltage

E011.0: motor overload

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismJudged by the motor overload curve
CauseVerificationRemedy
Motor-protection parameter F9-01 inappropriateCheck F9-01Set correctly; raising F9-01 extends motor overload time
Load too large or motor stalledCheck output current; check for stallReduce load and check the mechanics

E012.0: input phase loss

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismHardware signal indicates input phase loss
CauseVerificationRemedy
Input phase lossCheck RST wiring and that the three-phase input voltage is normalFix RST wiring and ensure three-phase input is normal

E013.0: output phase loss

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismAbove 0.8 Hz, the max/min ratio of three-phase output current averages exceeds 10×
CauseVerificationRemedy
System output phase lossCheck for output phase lossContact technical support

E013.1 / E013.2 / E013.3: U/V/W phase output phase loss

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismAbove 0.8 Hz, the max/min ratio of three-phase output current averages exceeds 10× and the corresponding phase is the minimum
CauseVerificationRemedy
Motor faultCheck that phase for open circuitRepair or replace the motor
Drive-to-motor cable abnormalCheck wiringFix external fault
Three-phase output unbalancedCheck three-phase output RMS currentInspect windings and fix
Drive board or IGBT abnormalOther causes cleared but fault persistsContact technical support
Output contactor fault or trippedCheck the output contactorReplace the output contactor

E014.0: drive overheat

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismHeatsink temperature above the overtemperature point
CauseVerificationRemedy
Ambient too highCheck ambient temperatureLower ambient
Air duct blockedCheck ductClear duct
Fan damagedCheck fanReplace fan
Module thermistor damagedStop and wait 1 h, then check temperatureReplace thermistor
Module damagedCheck for module damageContact technical support

E015.0: external fault

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismExternal terminal NC/NO fault
CauseVerificationRemedy
External fault via multi-function DICheck F4 parameters and DI physical stateClear external fault, confirm mechanism can restart, reset

E016.3: Modbus communication fault

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismCommunication break exceeds the timeout setting
CauseVerificationRemedy
Modbus timeoutCheck RS485 wiring; check Fd-04 and PLC cycleContact technical support

E017.0: contactor fault

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismHardware contactor-abnormal signal sampled continuously for 1 s
CauseVerificationRemedy
Contactor abnormalConfirm input is 342 V AC–418 V ACReplace contactor

E018.0: current-detection circuit fault

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismZero-drift detection exceeds 10% of rated current
CauseVerificationRemedy
Current-sampling abnormalMeasure three-phase UVW current at standstill; check if fluctuation exceeds 10% of ratedCheck that main power is on; Hall sensor or sampling circuit damaged—contact the manufacturer

E019.1: motor-parameter identification timeout

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismIdentification timed out
CauseVerificationRemedy
Identification timeoutVerify motor parameters (F1-00F1-05) and drive-model parameter (FF-01) against nameplateSet accurate nameplate values; motor may not be connected or output may have phase loss

E019.2: motor-parameter identification interrupted

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismIdentification was stopped before completion
CauseVerificationRemedy
Identification interruptedConfirm whether identification completedStop before completion; run identification again

E019.3: overcurrent during identification

ItemNotes
Default fault level0: coast to stop
ResettableYes
MechanismOvercurrent during identification

The above details the common ES750N fault codes. For a more complete list (including E043.x encoder-related, E077.x communication, E093.x STO, etc.), refer to the “Fault Alarms and Remedies” chapter of the original manufacturer manual.

Fault-code quick reference

CodeNameResettableCommon direction
E002.0Hardware overcurrentYesCheck grounding and encoder feedback
E002.2Software overcurrentYesCheck for short/ground, encoder, motor identification, acceleration time
E005.0OvervoltageYesCheck input voltage, encoder, braking resistor, acceleration time
E008.0Buffer-resistor faultYesCheck contactor and input-power stability
E009.1UndervoltageYesCheck input voltage, phase loss, contactor
E009.3Pre-drive timeoutYesWait for bus to stabilize; check power-on circuit
E010.0Drive overloadYesCheck load, drive sizing, motor identification
E011.0Motor overloadYesCheck F9-01, load
E012.0Input phase lossYesCheck RST wiring and input voltage
E013.0Output phase lossYesCheck output wiring
E013.1U-phase output phase lossYesCheck motor U phase and cable
E013.2V-phase output phase lossYesCheck motor V phase and cable
E013.3W-phase output phase lossYesCheck motor W phase and cable
E014.0Drive overheatYesCheck ambient, duct, fan
E015.0External faultYesCheck external DI state
E016.3Modbus communication faultYesCheck RS485 wiring and Fd-04
E017.0Contactor faultYesCheck contactor and input voltage
E018.0Current-detection circuit faultYesCheck main circuit and Hall sensor
E019.1Motor-parameter identification timeoutYesCheck motor and model parameters
E019.2Motor-parameter identification interruptedYesRe-run identification
E019.3Overcurrent during identificationYesCheck motor wiring and parameters